U2: fault trace, For a complete list of, U1 - 12 – Yaskawa Z1000 AC Drive HVAC User Manual

Page 310: U1 - 19

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-12

(4B)

Drive Status

Int Ctl Sts 1

Verifies the drive operation status.

U1 - 12=

00000000

During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection

1

1

1

1
1

1

1
1

No signal output

available

U1-13

(4E)

Terminal A1 Input Level Term A1 Level

Displays the signal level to analog input terminal A1.

10 V: 100%

0.1%

U1-14

(4F)

Terminal A2 Input Level Term A2 Level

Displays the signal level to analog input terminal A2.

10 V: 100%

0.1%

U1-16

(53)

Output Frequency after

Soft Starter

SFS Output

Displays output frequency with ramp time and S-curves. Units

determined by o1-03.

10 V: Max

frequency

0.01 Hz

U1-18

(61)

oPE Fault Parameter

OPE Error Code

Displays the parameter number that caused the oPE or Err

(EEPROM write error) error.

No signal output

available

U1-19

(66)

MEMOBUS/Modbus

Error Code

Transmit Err

Displays the contents of a MEMOBUS/Modbus error.

U1 - 19=

00000000

CRC Error
Data Length Error
Not Used

Parity Error
Overrun Error
Framing Error

Timed Out

Not Used

1

1

0

1

1

1

1

0

No signal output

available

U1-25

(4D)

Software Number

(Flash)

CPU 1 SW Number

FLASH ID

No signal output

available

U1-26

(5B)

Software No. (ROM)

CPU 2 SW Number

ROM ID

No signal output

available

U1-27

(7A8)

Message ID (OPR)

MessageID (OPR)

OPR ID

No signal output

available

U1-28

(7A9)

Message ID (INV)

MessageID (INV)

INV ID

No signal output

available

<1> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U2: Fault Trace

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U2-01

(80)

Current Fault

Current Fault

Displays the current fault.

No signal output

available

U2-02

(81)

Previous Fault

Last Fault

Displays the previous fault.

No signal output

available

U2-03

(82)

Frequency Reference at

Previous Fault

Frequency Ref

Displays the frequency reference at the previous fault.

No signal output

available

0.01 Hz

U2-04

(83)

Output Frequency at

Previous Fault

Output Freq

Displays the output frequency at the previous fault.

No signal output

available

0.01 Hz

U2-05

(84)

Output Current at

Previous Fault

Output Current

Displays the output current at the previous fault.

No signal output

available

<1>

<2>

B.13 U: Monitors

310

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising