5.7 Auto-Tuning Fault Detection

Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop. Auto-Tuning

faults do not trigger a multi-function digital output set for fault or alarm output.
An End error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in the

calculations. Restart Auto-Tuning after fixing the cause of the End error.
The drive may be used in the application if no cause can be identified despite the existence of an End error.
An Er error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the tables in

this section, and perform Auto-Tuning again after fixing the cause.

u

Auto-Tuning Codes, Causes, and Possible Solutions

Table 5.13 Auto-Tuning Codes, Causes, and Possible Solutions

HOA Keypad Display

Error Name

End3

Rated Current Setting Alarm (displayed after Auto-Tuning is complete)

Cause

Possible Solutions

The correct current rating printed on the motor

nameplate was not entered into T1-04

• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.

HOA Keypad Display

Error Name

End4

Adjusted Slip Calculation Error

Cause

Possible Solutions

The calculated slip is outside the allowable range Make sure the data entered for Auto-Tuning is correct.

HOA Keypad Display

Error Name

End5

Resistance Tuning Error

Cause

Possible Solutions

The calculated resistance value is outside the

allowable range

• Double-check the data entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.

HOA Keypad Display

Error Name

End7

No-Load Current Alarm

Cause

Possible Solutions

The entered no-load current value was outside the

allowable range

Check and correct faulty motor wiring.

Auto-Tuning results were less than 5% of the

motor rated current

Double-check the data entered for the Auto-Tuning process.

HOA Keypad Display

Error Name

Er-01

Motor Data Error

Cause

Possible Solutions

Motor data or data entered during Auto-Tuning

was incorrect

• Make sure motor data entered to T1- match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.

Motor output power and motor-rated current

settings (T1-02 and T1-04) do not match

• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.

Motor rated current and detected no-load current

are inconsistent

• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.

Base frequency and motor rated speed (T1-05 and

T1-07) do not match

• Correct the settings of parameters T1-05 and T1-07.
• Check that the correct number of poles were entered to T1-06.

5.7 Auto-Tuning Fault Detection