5.6 Programming Errors

u

Operator Programming Error Codes, Causes, and Possible Solutions

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an

inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not

trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to

Table 5.12

for the appropriate action. When

an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.

TERMS

TERMS

Digital Operator: Hand Off Auto (HOA) Keypad JVOP-183

Table 5.12 oPE Codes, Causes, and Possible Solutions

Digital Operator Display

Error Name

oPE01

Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.

Cause

Possible Solutions

The drive model selection (o2-04) and the actual capacity of the drive are

not the same.

Correct the value set to o2-04.

Digital Operator Display

Error Name

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.

Cause

Possible Solutions

Parameters were set outside the possible setting range.

Set parameters to the proper values.

Note:

When multiple errors occur simultaneously, other errors are given precedence over oPE02.

Digital Operator Display

Error Name

oPE03

Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01

to H1-08.

Cause

Possible Solutions

• The same function is assigned to two multi-function inputs.
• Excludes “Not used” and “External Fault.”

• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.

The Up command was set but the Down command was not, or vice versa

(settings 10 vs. 11).

Properly set the functions that required for use in combination with other

functions.

The Up 2 command was set but the Down 2 command was not, or vice versa

(settings 75 vs. 76).
• Run/Stop command for a 2-wire sequence was set (H1- = 42), but

Forward/Reverse command (H1- = 43) was not.

• “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or

H1-02 = 6A).

Properly set the functions that required for use in combination with other

functions.

Two of the following functions are set simultaneously:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)

• Check if contradictory settings have simultaneously been assigned to the

multi-function input terminals.

• Correct setting errors.

The Up/Down command (10, 11) and PID control (b5-01) are enabled

simultaneously.

Set b5-01 to 0 to disable control PID or disable the Up/Down command.

5.6 Programming Errors

218