O2: hoa keypad functions – Yaskawa Z1000 AC Drive HVAC User Manual

Page 299

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o1-15

(3107)

Frequency Reference

and Frequency Related

Monitor Custom Units 3

Fref Cust Unit 3

Sets the customer-specified unit display for the frequency

reference parameters and frequency related monitors when

o1-03 = 3 and o1-09 = 15 as custom units

Default: 41

Range: 30 to 7A

182

o1-16

(3108)

F1 Key Function

Selection

F1 Key Func Sel

0: Standard

1: Mon

2: DRV/BYP

3: RUN BYP

4: RLY

Selects the function of the F1 key and the LCD display text

above the F1 key.

0: Standard

1: Monitor

2: Drive/Bypass (DRV/BYP)

3: Bypass Run Command (RUN BYP)

4: Toggle Relay Output (RLY)

Default: 0

Range: 0 to 4

182

o1-17

(3109)

F2 Key Function

Selection

F2 Key Func Sel

0: Standard

1: Mon

2: DRV/BYP

3: RUN BYP

4: RLY

Selects the function of the F1 key and the LCD display text

above the F1 key.

0: Standard

1: Monitor

2: Drive/Bypass (DRV/BYP)

3: Bypass Run Command (RUN BYP)

4: Toggle Relay Output (RLY)

Default: 0

Range: 0 to 4

182

o1-18

(310A)

User Defined Parameter

Upper

Userdefined par1

Allows the user to set values that can be used as reference

information.

Default: 0

Range: 0 to 999

182

o1-19

(310B)

User Defined Parameter

Lower

Userdefined par2

Allows the user to set values that can be used as reference

information.

Default: 0

Range: 0 to 999

182

<1> Default setting is dependent on parameter o1-03, HOA Keypad Display Selection.

u

o2: HOA Keypad Functions

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o2-02

(506)

OFF Key Function

Selection

Oper STOP Key

0: Disabled

1: Enabled

0: Disabled. OFF key is disabled in REMOTE operation.

1: Enabled. OFF key is always enabled.

Default: 1

Range: 0, 1

183

o2-03

(507)

User Parameter Default

Value

User Default Sel

0: No Change

1: Save User Init

2: Clear User Init

0: No change.

1: Set defaults. Saves parameter settings as default values for a

User Initialization.

2: Clear all. Clears the default settings that have been saved for

a User Initialization.

Default: 0

Range: 0 to 2

134

o2-04

(508)

Drive Model Selection Inverter Model #

Enter the drive model. Setting required only if installing a new

control board.

Default:

Determined by

drive capacity

183

o2-05

(509)

Frequency Reference

Setting Method

Selection

Oper Ref Method

0: Disabled

1: Enabled

0: ENTER key must be pressed to enter a frequency reference.

1: ENTER key is not required. The frequency reference can be

adjusted using the up and down arrow keys only.

Default: 0

Range: 0, 1

135

o2-06

(50A)

Operation Selection

when HOA Keypad is

Disconnected

Oper Discon Det

0: Disabled

1: Enabled

0: The drive continues operating if the HOA keypad is

disconnected.

1: An oPr fault is triggered and the motor coasts to stop.

Default: 1

Range: 0, 1

183

o2-07

(527)

Motor Direction at

Power Up when Using

Operator

For/RevSel@PwrUp

0: Forward

1: Reverse

0: Forward

1: Reverse

This parameter requires assigning drive operation to the HOA

keypad.

Default: 0

Range: 0, 1

183

o2-19

(61F)

Selection of Parameter

Write during Uv

ParameterSet Sel

0: Disabled

1: Enabled

Selects whether parameter settings can be changed during a DC

bus undervoltage condition. Used with 24 V Power Supply (PS-

A10L, PS-A10H).

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

B.10 o: Operator-Related Settings

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

299