Digital Operator Display

Minor Fault Name

EF1

External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.

EF2

External fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

External fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

External fault (input terminal S7)
External fault at multi-function input terminal S7.

Cause

Possible Solutions

An external device has tripped an alarm

function.

Remove the cause of the external fault and reset the multi-function input value.

Wiring is incorrect.

• Ensure the signal lines have been connected properly to the terminals assigned for external fault detection

(H1- = 2C to 2F).

• Reconnect the signal line.

Multi-function contact inputs are set

incorrectly.

• Check if the unused terminals have been set for H1- = 2C to 2F (External Fault).
• Change the terminal settings.

Digital Operator Display

Minor Fault Name

EoF

EoF

Emergency Override Forward Run

Cause

Possible Solution

The multi-function digital input for

EmergOverrideFWD (H1- = AF) has

been closed.

Open H1- = AF if the emergency condition is no longer present

Digital Operator Display

Minor Fault Name

Eor

Eor

Emergency Override Reverse Run

Cause

Possible Solution

The multi-function digital input for

EmergOverrideREV (H1- = B0) has

been closed.

Open H1- = B0 if the emergency condition is no longer present

Digital Operator Display

Minor Fault Name

FbH

Excessive PID Feedback
The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and b5-12

is set to 1 or 4.

Cause

Possible Solutions

Parameter settings for b5-36 and b5-37 are

incorrect.

Check parameters b5-36 and b5-37.

PID feedback wiring is faulty.

Correct the wiring.

Feedback sensor has malfunctioned.

Check the sensor and replace it if damaged.

Feedback input circuit is damaged.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

Digital Operator Display

Minor Fault Name

FbL

PID Feedback Loss
The PID feedback input is lower than the level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solutions

Parameter settings for b5-13 and b5-14 are

incorrect.

Check parameters b5-13 and b5-14.

5.5 Alarm Detection

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

213

5

Troubleshooting