Yaskawa Z1000 AC Drive HVAC User Manual

Page 252

Advertising
background image

u

Three-Phase 600 V Class Drive Models 5A0125 to 5A0242

Table A.3 Power Ratings Continued (Three-Phase 600 V Class)

Item

Specification

Drive Models

5A0125

5A0145

5A0192

5A0242

Maximum Applicable Motor Capacity (HP)

<1>

125

150

200

250

Input

Input Current (A)

<2>

129

158

228

263

Rated Voltage

Rated Frequency

Three-phase 500 to 600 Vac 50/60 Hz

Allowable Voltage Fluctuation

-10 (-15) to +10%

Allowable Frequency Fluctuation

±5%

Input Power (kVA)

147

181

261

301

Output

Rated Output Capacity (kVA)

<3>

<4>

124

144

191

241

Rated Output Current (A)

<4>

125

145

192

242

Overload Tolerance

110% of rated output for 60 s

140% of rated output for 0.5 s

Carrier Frequency

User adjustable between 2 and 3kHz

Maximum Output Voltage (V)

Three-phase 500 to 600 Vac (proportional to input voltage)

Maximum Output Frequency (Hz)

240 Hz

<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than

the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.

A.1 Power Ratings

252

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual