Yaskawa Z1000 AC Drive HVAC User Manual
Page 252
u
Three-Phase 600 V Class Drive Models 5A0125 to 5A0242
Table A.3 Power Ratings Continued (Three-Phase 600 V Class)
Item
Specification
Drive Models
5A0125
5A0145
5A0192
5A0242
Maximum Applicable Motor Capacity (HP)
<1>
125
150
200
250
Input
Input Current (A)
<2>
129
158
228
263
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation
-10 (-15) to +10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
147
181
261
301
Output
Rated Output Capacity (kVA)
<3>
<4>
124
144
191
241
Rated Output Current (A)
<4>
125
145
192
242
Overload Tolerance
110% of rated output for 60 s
140% of rated output for 0.5 s
Carrier Frequency
User adjustable between 2 and 3kHz
Maximum Output Voltage (V)
Three-phase 500 to 600 Vac (proportional to input voltage)
Maximum Output Frequency (Hz)
240 Hz
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.1 Power Ratings
252