H4: analog outputs – Yaskawa Z1000 AC Drive HVAC User Manual

Page 288

Advertising
background image

H3 Multi-Function Analog Input Settings

H3-

Setting

Function

LCD Display

Description

Page

4

Output voltage bias

Voltage Bias

10 V = E1-05 (motor rated voltage)

5

Accel/decel time gain

Acc/Dec Change

10 V = 100%

6

DC Injection Braking

current

DC Brake Current

10 V = Drive rated current

7

Overtorque/undertorque

detection level

Torque Det Level

10 V = Drive rated current (V/f)

10 V = Motor rated torque (OLV/PM)

8

Stall Prevention level

during run

Stall Prev Level

10 V = Drive rated current

9

Output frequency lower

limit level

Ref Lower Limit

10 V = E1-04 (maximum output frequency)

B

PI feedback

PID Feedback1

10 V = 100%

170

C

PI setpoint

PID Set Point

10 V = 100%

170

D

Frequency bias

Freq Ref Bias 2

10 V = E1-04 (maximum output frequency)

170

E

Motor temperature (PTC

input)

Motor PTC

10 V = 100%

F

Through mode

Not Used

Set this value when using the terminal in the pass-through mode.

16

Differential PI feedback PID Feedback 2

10 V = 100%

25

Secondary PI Setpoint

PI2 Setpoint

10 V = S3-02 (maximum output frequency)

26

Secondary PI Feedback PI2 Feedback

10 V = S3-02 (maximum output frequency)

u

H4: Analog Outputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H4-01

(41D)

Multi-Function Analog

Output Terminal FM

Monitor Selection

Term FM FuncSel

Selects the data to be output through multi-function analog

output terminal FM.

Set the desired monitor parameter to the digits available in

U-.

For example, enter “103” for U1-03.

Default: 102

Range: 000 to

655

H4-02

(41E)

Multi-Function Analog

Output Terminal FM

Gain

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the

selected monitor value.

Default: 100.0%

Min.: -999.9

Max.: 999.9

H4-03

(41F)

Multi-Function Analog

Output Terminal FM

Bias

Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

H4-04

(420)

Multi-Function Analog

Output Terminal AM

Monitor Selection

Terminal AM Sel

Selects the data to be output through multi-function analog

output terminal AM.

Set the desired monitor parameter to the digits available in

U-.

For example, enter “103” for U1-03.

Default: 103

Range: 000 to

655

H4-05

(421)

Multi-Function Analog

Output Terminal AM

Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of

the selected monitor value.

Default: 50.0%

Min.: -999.9

Max.: 999.9

H4-06

(422)

Multi-Function Analog

Output Terminal AM

Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the

selected monitor value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

H4-07

(423)

Multi-Function Analog

Output Terminal FM

Signal Level Selection

Level Select1

0: 0-10 VDC

2: 4-20 mA

0: 0 to 10 V

2: 4 to 20 mA

Default: 0

Range: 0, 2

H4-08

(424)

Multi-Function Analog

Output Terminal AM

Signal Level Selection

AO Level Select2

0: 0-10 VDC

2: 4-20 mA

0: 0 to 10 V

2: 4 to 20 mA

Default: 0

Range: 0, 2

B.7 H Parameters: Multi-Function Terminals

288