3.9 Control Circuit Wiring

u

Control Circuit Connection Diagram

Refer to

Figure 3.1

on page

71

when wiring terminals on the drive control circuit.

u

Control Circuit Connections

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S7), multi-function digital outputs

(M1 to M4), multi-function analog inputs (A1 to A3), and multi-function analog monitor output (FM, AM). The default setting

is listed next to each terminal in

Figure 3.1

on page

71

.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with

untested control circuits could result in death or serious injury.

WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter

A1-06 may change the I/O terminal function automatically from the factory setting. Failure to comply may result in death or serious injury.

n

Input Terminals

Table 3.4

lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.

Table 3.4 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Multi-Function

Digital Inputs

S1

Multi-function input 1

(Closed: Forward run, Open: Stop)

• Photocoupler
• 24 Vdc, 8 mA

Refer to Sinking/Sourcing Mode for Digital Inputs on page

92

.

281

S2

Multi-function input 2

(Closed: Reverse run, Open: Stop)

S3

Multi-function input 3

(External fault, N.O.)

S4

Multi-function input 4

(Fault reset)

S5

Multi-function input 5

(Multi-step speed reference 1)

S6

Multi-function input 6

(Multi-step speed reference 2)

S7

Multi-function input 7

(Jog reference)

SC

Multi-function input common

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs, 150 mA max (only when not

using digital input option DI-A3)

NOTICE: Do not jumper or short terminals SP and SN. Failure

to comply will damage the drive.

92

SN

Digital input power supply 0 V

92

Analog Inputs /

Pulse Train

Input

+V

Power supply for analog inputs

10.5 Vdc (max allowable current 20 mA)

121

A1

Multi-function analog input 1

(Frequency reference bias)

-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)

121

169

A2

Multi-function analog input 2

(Frequency reference bias)

• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
• 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
• Voltage or current input must be selected by DIP switch S1 and

H3-09.

121

121

169

AC

Frequency reference common

0 V

121

FE

Ground for shielded lines and option cards

3.9 Control Circuit Wiring

86

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual