U5: pi monitors, For a complete list of u5 – Yaskawa Z1000 AC Drive HVAC User Manual

Page 314

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-21

(7DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

0 = OFF

1 = AUTO

2 = HAND

Y: Input power supply data

0 = HOA keypad

1 = External terminals

3 = Serial communications (APOGEE FLN, BACnet,

MEMOBUS/Modbus, or Metasys N2)

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, HOA keypad)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(7DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(7DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PI Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U5-01

(57)

PI Feedback

PID Feedback 1

Displays the PI feedback value.

10 V: 100%

0.01%

U5-02

(63)

PI Input

PID Input

Displays the amount of PI input (deviation between PI setpoint

and feedback).

10 V: 100%

0.01%

U5-03

(64)

PI Output

PID Output

Displays PI control output.

10 V: 100%

0.01%

U5-04

(65)

PI Setpoint

PID Setpoint

Displays the PI setpoint.

10 V: 100%

0.01%

U5-05

(7D2)

PI Differential Feedback PID Feedback 2

Displays the second PI feedback value if differential feedback is

used (H3- = 16).

10 V: 100%

0.01%

U5-06

(7D3)

PI Adjusted Feedback

PID Diff Fdbk

Displays the difference of both feedback values if differential

feedback is used (U5-01 - U5-05).

If differential feedback is not used, then U5-01 and U5-06 will

be the same.

10 V: 100%

0.01%

U5-07

(72)

AUTO Mode Frequency

Reference Value

AUTO mode Fref

Displays the Frequency reference value at AUTO Mode.

No signal output

available

0.01 Hz

U5-08

(73)

HAND Mode Frequency

Reference Value

HAND mode Fref

Displays the Frequency reference value at HAND Mode.

No signal output

available

0.01 Hz

U5-14

(86B)

PI Output Upper 4 Digits PI Output U4

Displays Custom PI output. U5-14 shows the upper 4 digits.

10V: (b5-43 x
10000) + b5-44

<1>

1

U5-15

(86C)

PI Output Lower 4 Digits PI Output L4

Displays Custom PI output. U5-15 shows the lower 4 digits.

No signal output

available

0.01

U5-17

(302A) PI2 Setpoint

PI2 Set-point

Displays the secondary PI setpoint.

10 V: Max

frequency

0.01%

B.13 U: Monitors

314