Wiring diagram for multiple connections, Network termination – Yaskawa Z1000 AC Drive HVAC User Manual

Page 321

Advertising
background image

u

Wiring Diagram for Multiple Connections

Figure C.3

explains the wiring diagrams for multiple connections using BACnet communication.

n

RS-485 Interface

Drive

Drive

Drive

S2

S2

S2

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

R–
R+
S–
S+
IG

PLC

OFF

OFF

ON

Figure C.3 RS-485 Interface

Note:

1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other

slave devices.

2. Set H5-07 to 1 when using the RS-485 interface.

u

Network Termination

The two ends of the BACnet network line have to be terminated. The drive has a built in termination resistor that can be enabled

or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the termination resistor by setting

DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not located at the network line end.

C.3 Connecting to a Network

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual