4.6 Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these

Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to values

appropriate for the application that was selected.
An Application Preset can either be selected from the Application Selection display in the Setup Group (

Refer to Using the

Setup Group on page 111

) or in parameter A1-06. The following presets can be selected:

Note:

An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to initialize

the drive by setting A1-03 to “2220” or “3330” prior to selecting an Application Preset.

WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the

I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.

No.

Parameter Name

Setting Range

Default

A1-06

Application Presets

0: Standard

1: Fan

2: Fan with PI Control

3: Return Fan with PI Control

4: Cooling Tower Fan

5: Cooling Tower Fan with PI Control

6: Pump (Secondary)

7: Pump with PI Control

0

u

HVAC Application Parameters

In addition, the application parameters most likely to be changed for fan and pump applications are assigned to the group of

User Parameters, A2-01 through A2-32. User Parameters provide quicker access to by eliminating the need to scroll through

multiple menus.

Table 4.7 User Parameters (A2-01 to A2-32)

No.

Parameter Name

No.

Parameter Name

b1-03

Stopping Method Selection

C1-01

Acceleration Time 1

b1-04

Reverse Operation Selection

d2-03

Master Speed Reference Lower Limit

b2-09

Motor Pre-Heat Current 2

H1-07

Multi-Function Digital Input Terminal S7 Function

Selection

b5-01

PI Function Setting

H3-01

Terminal A1 Signal Level Selection

b5-03

Integral Time Setting (I)

H3-02

Terminal A1 Function Selection

b5-08

PI Primary Delay Time Constant

H3-10

Terminal A2 Function Selection

b5-09

PI Output Level Selection

L5-01

Number of Auto Restart Attempts

b5-13

PI Feedback Low Detection Level

L6-01

Stall Prevention Selection during Deceleration

b5-14

PI Feedback Low Detection Time

o1-06

User Monitor Selection Mode

b5-15

PI Sleep Function Start Level

o1-07

Second Line Monitor Selection

b5-16

PI Sleep Delay Time

o1-08

Third Line Monitor Selection

u

Setting 1: Fan Application

Table 4.8 Fan: Parameter Settings

No.

Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

1: Reverse operation disabled

C1-01

Acceleration Time 1

60 s

L5-01

Number of Auto Restart Attempts

10

L6-01

Torque Detection Selection 1

5: UL3 at speed agree (Alarm)

4.6 Application Selection

118

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual