C.9 Communication Errors

Errors that may occur when accessing drive parameters using the BACnet objects are shown in

Table C.12

.

Table C.12 MEMOBUS to BACnet Error Conversion

Error Code

Description

03d

BN_ERR_DEVICE_IS_BUSY

Writing to a parameter was attempted while the drive was saving parameters to non-volatile memory.

27d

BN_ERR_READ_ACCESS_DENIED

Invalid parameter register number used when reading.

37d

BN_ERR_VALUE_OUT_OF_RANGE

Value written to the parameter is out of the valid range.

40d

BN_ERR_WRITE_ACCESS_DENIED

An invalid parameter register number was used when writing.

Writing to a parameter was attempted while the drive was in a mode that disables writing (i.e., writing while the drive was

Auto-Tuning).

Writing to a parameter was attempted while the DC Bus had an Undervoltage (Uv) fault

C.9 Communication Errors

334