A.4 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Rated Current Depending on Carrier Frequency

The tables below show the drive output current depending on the carrier frequency settings.
The 2 kHz values shown in

Table A.5

are equal to the drive rated current shown on the drive nameplate. Increasing the carrier

frequency above 2 kHz will reduce the rated output current of the drive.

Table A.5 Three-Phase 600 V Class Carrier Frequency and Current Derating

Three-Phase 600 V Class

Drive Model

Rated Current [A]

2 kHz

8 kHz

10 kHz

15 kHz

5A0003

2.7

2.2

2.0

1.3

5A0004

3.9

3.4

3.1

2.1

5A0006

6.1

4.9

4.3

2.9

5A0009

9

7.5

6.6

4.5

5A0011

11

9.3

8.2

5.6

5A0017

17

13.3

11.8

5A0022

22

17.0

15.1

5A0027

27

22.0

19.5

5A0032

32

27.3

24.4

Three-Phase 600 V Class

Drive Model

Rated Current [A]

2 kHz

5 kHz

8 kHz

10 kHz

5A0041

41.0

39.7

33.5

29.4

5A0052

52.0

50.3

42.5

37.3

5A0062

62.0

61.3

49.7

41.9

5A0077

77.0

76.2

61.7

52.0

5A0099

99.0

80.0

55.1

Three-Phase 600 V Class

Drive Model

Rated Current [A]

2 kHz

3 kHz

5A0125

125.0

93.0

5A0145

145.0

108.0

5A0192

192.0

148.0

5A0242

242.0

187.0

A.4 Drive Derating Data

256