Yaskawa Z1000 AC Drive HVAC User Manual

Page 129

Advertising
background image

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

Determined by

o2-04

Note:

1. Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly

to prevent this error.

n

E2-11: Motor Rated Power

Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be

saved to E2-11.

No.

Parameter Name

Setting Range

Default

E2-11

Motor Rated Power

0.00 to 650.00 kW

Determined by

o2-04

n

E5-02: Motor Rated Power

Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.

No.

Parameter Name

Setting Range

Default

E5-02

Motor Rated Power

0.10 to 370.00 kW

Determined by

o2-04

n

E5-03: Motor Rated Current

Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.

No.

Parameter Name

Setting Range

Default

E5-03

Motor Rated Current

10 to 200% of drive rated

current

Determined by

o2-04

Note:

Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.

n

E5-04: Number of Motor Poles

Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.

No.

Parameter Name

Setting Range

Default

E5-04

Number of Motor Poles

2 to 48

Determined by

o2-04

n

E5-05: Motor Stator Resistance (r1)

Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance

manually.

No.

Parameter Name

Setting Range

Default

E5-05

Motor Stator Resistance

0.000 to 65.000 Ω

Determined by

o2-04

n

E5-06: Motor d-Axis Inductance (Ld)

Sets the d-Axis inductance in 0.01 mH units.

No.

Parameter Name

Setting Range

Default

E5-06

Motor d-Axis Inductance

0.00 to 300.00 mH

Determined by

o2-04

4.7 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

129

4

Start-Up Programming & Operation