Yaskawa Z1000 AC Drive HVAC User Manual

Page 199

Advertising
background image

Digital Operator Display

Fault Name

or

CPF11 to CPF14

CPF16 to CPF19

Control Circuit Error

Cause

Possible Solution

There is a self-diagnostic error in the control

circuit

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Connector on the operator is damaged

Replace the operator.

Digital Operator Display

Fault Name

CPF02

A/D Conversion Error
An A/D conversion error or control circuit error occurred.

Cause

Possible Solution

Control circuit is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

CPF03

Control Board Connection Error
Connection error between the control board and the drive

Cause

Possible Solution

There is a connection error

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Drive fails to operate properly due to electrical

signal interference

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the

drive input power side.

• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if

required.

• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive

power supply input.

Digital Operator Display

Fault Name

CPF06

EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution

There is an error in EEPROM control circuit

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

The power supply was switched off while

parameters were being saved to the drive

Reinitialize the drive (A1-03 = 2220, 3330).

Digital Operator Display

Fault Name

CPF07

Terminal Board Connection Error

CPF08

Cause

Possible Solution

There is a faulty connection between the

terminal board and the control board

• Turn off the power and reconnect the terminal board.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

or

CPF20 or CPF21

Control Circuit Error

Cause

Possible Solution

Hardware is damaged

• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

5.4 Fault Detection

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

199

5

Troubleshooting

Advertising