Terminal fm/am signal selection, Memobus/modbus termination, Jumper s5 – Yaskawa Z1000 AC Drive HVAC User Manual
Page 94: Refer to terminal fm, Refer to memobus, 10 control i/o connections
u
Terminal FM/AM Signal Selection
The signal type for terminals FM and AM can be set to either voltage or current output using jumper S5 on the terminal board
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Table 3.14 Jumper S5 Settings
Terminal
Voltage Output
Current Output
Terminal FM
AM
FM
V
I
AM
FM
V
I
Terminal AM
AM
FM
V
I
AM
FM
V
I
Table 3.15 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal FM signal level selection
0: 0 to 10 Vdc
2: 4 to 20 mA
0, 2
0
H4-08
Terminal AM signal level selection
u
MEMOBUS/Modbus Termination
This drive is equipped with a built-in termination resistor for the RS-422/485 communication port. DIP switch S2 enables or
disabled the termination resistor as shown in
. The OFF position is the default. The termination resistor should be
placed to the ON position when the drive is the last in a series of slave drives.
Refer to Switches and Jumpers on the Terminal
to locate switch S2.
Table 3.16 MEMOBUS/Modbus Switch Settings
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (default setting)
3.10 Control I/O Connections
94