S4: bypass operation, S5: hoa keypad parameters – Yaskawa Z1000 AC Drive HVAC User Manual

Page 305

Advertising
background image

u

S4: Bypass Operation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S4-01

(322B) BP Auto Transfer on

Fault Enable

BP Fault Trnsfer

0: Disabled

1: Enabled

0: No transfer after fault

1: Transfer to bypass after fault

Default: 1

Range: 0, 1

S4-02

(322C) Secondary PI User

Display

BP Enrgy Sav Lvl

Delta used to determine when to switch into Energy Save Bypass.

This allows for lower frequency output values to also trigger

Energy Save Bypass functionality.

Default: 0 Hz

Min.: 0

Max.: 20

S4-03

(322D) BP Energy Save Bypass

Timer

BP Enrgy Sav TMR

Sets the time in seconds that the drive should run at the specified

speed before entering Energy Save Bypass mode.

Default: 60 s

Min.: 10

Max.: 60000

S4-04

(322E) BP Energy Save Bypass

Speed Increase

BP Enrgy Sav Inc

Sets the value in Hz that the drive will increase the output

frequency above E1-04 before performing an Energy Save

transfer to bypass.

Default: 6 Hz

Min.: 0

Max.: 10

u

S5: HOA Keypad Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S5-01

(322F)

HAND Frequency

Reference Selection

HAND Fref Source

0: Operator

1: Terminals

2: d1-16

3: S5-05

4: Set by b1-01

0: HOA keypad

1: Terminals

2: d1-16

3: S5-05

4: Determined by b1-01

Default: 0

Range: 0 to 4

S5-02

(3230)

HAND/AUTO During

Run Selection

HAND/AUTO

@Run

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

S5-03

(3231)

HAND Mode PI

Selection

HAND Mode PI Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

S5-04

(3232)

HAND Mode Behavior

Selection

HAND BehaviorSel

0: Legacy

1: Normal

2: Normal w/

Memory

0: Legacy operation mode

1: Normal operation mode

2: Normal with memory

Note:

The drive will always be in AUTO mode at power

up with S5-04 = 1.

Default: 1

Range: 0 to 2

S5-05

(3233)

HAND Frequency

Reference 1

HAND Freq Ref 2

Sets the frequency reference used in HAND mode when S5-01 is

set to 2.

Default: 0.00

Hz

Min.: 0.00

Max.: 240.00

S5-07

(3235)

HAND Key Function

Selection (HOA

Keypad)

Oper HAND Key

0: Disabled

1: Enabled

Determines whether the HAND key on the HOA keypad will be

enabled for switching between HAND and AUTO.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

B.11 S: Special Application

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

305

B

Parameter List

Advertising