Yaskawa Z1000 AC Drive HVAC User Manual

Page 170

Advertising
background image

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

n

Multi-Function Analog Input Terminal Settings

See

Table 4.38

for information on how H3-02 and H3-10 determine functions for terminals A1 and A2.

Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting

and adjusting analog input functions.

Table 4.38 Multi-Function Analog Input Terminal Settings

Setting

Function

Page

0

Frequency Bias

170

1

Frequency Gain

170

2

Auxiliary Frequency Reference 1

170

3

Auxiliary Frequency Reference 2

170

4

Output Voltage Bias

5

Accel/Decel Time Gain

6

DC Injection Braking Current

7

Overtorque/Undertorque Detection Level

8

Stall Prevention Level During Run

Setting

Function

Page

9

Output Frequency Lower Limit Level

B

PI Feedback

170

C

PI Setpoint

170

D

Frequency Bias

170

E

Motor Temperature (PTC Input)

170

F

Through Mode

171

16

Differential PI Feedback

171

25

Secondary PI Setpoint

26

Secondary PI Feedback

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input

terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog

input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 164

for details.

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 164

for details.

Setting B: PI Feedback

Supplies the PI feedback value. This setting requires PI operation to be enabled in b5-01.

Setting C: PI Setpoint

Supplies the PI setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PI setpoint. PI

operation to be enabled in b5-01 to use this setting.

Setting D: Frequency Bias

The input value of an analog input set to this function will be added to the frequency reference. This function can be used with

any frequency reference source.

Setting E: Motor Temperature

In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient) thermistor

for motor insulation protection.

4.13 Advanced Drive Setup Adjustments

170

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

Advertising