General description, Z1000 model selection, Control mode selection – Yaskawa Z1000 AC Drive HVAC User Manual

Page 23: 2 general description

Advertising
background image

1.2 General Description

u

Z1000 Model Selection

Refer to

Table 1.1

for drive selection depending on the motor power and Normal Duty (ND) or Heavy Duty (HD) rating.

Note:

The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher

ambient temperatures require derating.

Table 1.1 Z1000 Models

Motor Power

HP

Drive Model

Rated Output Current (A)

<1>

2

5A0003

2.7

3

5A0004

3.9

5A0006

6.1

7.5

5A0009

9

10

5A0011

11

15

5A0017

17

20

5A0022

22

25

5A0027

27

30

5A0032

32

40

5A0041

41

50

5A0052

52

60

5A0062

62

75

5A0077

77

100

5A0099

99

125

5A0125

125

150

5A0145

145

200

5A0192

192

250

5A0242

242

<1> These values assume the carrier frequency is set to 2 kHz.

Note:

Current derating is required when setting the carrier frequency higher.

Refer to Carrier Frequency Derating on page 257

for details.

u

Control Mode Selection

Table 1.2

gives an overview of the Z1000 control modes and the various features associated with those control modes.

Table 1.2 Control Modes and Features

Motor Type

Induction Motors

Permanent Magnet Motors

Comments

Control Mode

V/f

OLV/PM

Parameter Setting

A1-02 = 0

A1-02 = 5

Default Setting is V/f control (A1-02 = 0)

Basic Description

V/f control

Open Loop Vector control

for PM motors

Type of

Applications

Motor Type

IM

PM

Multi Motor

YES

Motor data unknown

YES

High Speed Accuracy

YES

Control

Characteristics

Speed Control Range

1:40

1:20

May fluctuate with characteristics and motor
temperature.

Speed Accuracy

±2 to 3%

±0.2%

Speed deviation when operating at constant speed
may fluctuate with characteristics and motor
temperature.

Speed Response

3 Hz (approx.)

10 Hz

Max. frequency of a speed reference signal that the
drive can follow may fluctuate with characteristics
and motor temperature.

Starting Torque

140% at 3 Hz

100% at

5% speed

Starting torque may fluctuate with characteristics and
motor temperature.
Performance may differ by capacity.

1.2 General Description

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

23

1

Receiving

Advertising