A.3 Drive Watt Loss Data

Table A.4 Watt Loss Three-Phase 600 V Class Three-Phase Models

Drive Model

Normal Duty

Rated Amps (A)

<1>

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

5A0003

2.7

23.3

21.5

44.8

5A0004

3.9

33.6

27.5

61.1

5A0006

6.1

43.7

28.1

71.8

5A0009

9.0

68.9

43.4

112.3

5A0011

11

88.0

56.1

144.0

5A0017

17

146.7

96.6

243.2

5A0022

22

178.3

99.4

277.7

5A0027

27

227.2

132.1

359.3

5A0032

32

279.9

141.6

421.5

5A0041

41

330.8

136.2

467.0

5A0052

52

427.8

166.2

594.0

5A0062

62

791.2

279.0

1070.2

5A0077

77

959.1

329.4

1288.6

5A0099

99

1253.2

411.7

1664.9

5A0125

125

1641

537

2178

5A0145

145

1860

603

2463

5A0192

192

2420

769

3189

5A0242

242

3100

1131

4231

<1> Value assumes the carrier frequency is set to 2 kHz.