Refer to, Minor faults and alarms, Operation errors – Yaskawa Z1000 AC Drive HVAC User Manual
Page 196
<1> Displayed as CPF00 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
CPF01.
<2> Displayed as CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
CPF21.
<3> Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
n
Minor Faults and Alarms
important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger a
digital output programmed for alarm output (H2- = 10). A fault (not an alarm) is present if the ALM LED lights without
blinking.
for information on fault codes.
Table 5.6 Minor Fault and Alarm Displays
HOA
Keypad
Display
Name
Minor Fault
Output
(H2- = 10)
Page
bAT
HOA Keypad Battery Voltage Low
YES
bb
Drive Baseblock
No output
boL
Braking Transistor Overload Fault
YES
bUS
Option Card Communications
Error
YES
CALL
Serial Communication
Transmission Error
YES
CE
MEMOBUS/Modbus
Communication Error
YES
CrST
Cannot Reset
YES
dnE
Drive Disabled
YES
E5
SI-T3 Watchdog Timer Error
YES
EoF
Emergency Override Forward Run
YES
Eor
Emergency Override Reverse Run
YES
EF
Run Command Input Error
YES
EF0
Option Card External Fault
YES
EF1 to EF7 External Fault
(input terminal S1 to S7)
YES
FbH
Excessive PID Feedback
YES
FbL
PID Feedback Loss
YES
HCA
Current Alarm
YES
LT-1
Cooling Fan Maintenance Time
No output
<1>
HOA
Keypad
Display
Name
Minor Fault
Output
(H2- = 10)
Page
LT-2
Capacitor Maintenance Time
No output
<1>
LT-3
Soft Charge Bypass Relay
Maintenance Time
No output
<1>
LT-4
IGBT Maintenance Time (50%)
No output
<1>
oH
Heatsink Overheat
YES
oH2
Drive Overheat
YES
oH3
Motor Overheat
YES
oL3
Overtorque 1
YES
ov
Overvoltage
YES
PASS
MEMOBUS/Modbus Test Mode
Complete
No output
SE
MEMOBUS/Modbus Test Mode
Fault
YES
TdE
Time Data Error
YES
TIE
Time Interval Error
YES
TrPC
IGBT Maintenance Time (90%)
YES
UL3
Undertorque Detection 1
YES
UL6
Motor Underload
YES
Uv
Undervoltage
YES
wRUn
Run Delay Timer is Active
YES
<1> Output when H2- = 2F.
n
Operation Errors
Table 5.7 Operation Error Displays
HOA
Keypad
Display
Name
Page
oPE01
Drive Unit Setting Error
oPE02
Parameter Setting Range Error
oPE03
Multi-Function Input Setting Error
oPE04
Terminal Board Mismatch Error
oPE05
Run Command Selection Error
oPE07
Multi-Function Analog Input Selection Error
oPE08
Parameter Selection Error
HOA
Keypad
Display
Name
Page
oPE09
PID Control Selection Error
oPE10
V/f Data Setting Error
oPE11
Carrier Frequency Setting Error
oPE13
Pulse Train Monitor Selection Error
oPE16
Energy Saving Constants Error
oPE27
BP Program Error
oPE28
Sequence Timer Error
5.3 Drive Alarms, Faults, and Errors
196
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual