B.7 H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

u

H1: Multi-Function Digital Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H1-01

(438)

Multi-Function Digital

Input Terminal S1

Function Selection

Term S1 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 40 (F)

<1>

Min.: 1

Max.: B2

H1-02

(439)

Multi-Function Digital

Input Terminal S2

Function Selection

Term S2 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 41 (F)

<1>

Min.: 1

Max.: B2

H1-03

(400)

Multi-Function Digital

Input Terminal S3

Function Selection

Term S3 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 24

Min.: 0

Max.: B2

H1-04

(401)

Multi-Function Digital

Input Terminal S4

Function Selection

Term S4 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 14

Min.: 0

Max.: B2

H1-05

(402)

Multi-Function Digital

Input Terminal S5

Function Selection

Term S5 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 3 (0)

<1>

Min.: 0

Max.: B2

H1-06

(403)

Multi-Function Digital

Input Terminal S6

Function Selection

Term S6 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 4 (3)

<1>

Min.: 0

Max.: B2

H1-07

(404)

Multi-Function Digital

Input Terminal S7

Function Selection

Term S7 Func Sel

Assigns a function to the multi-function digital inputs.

Refer to pages

281

to

284

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 6 (4)

<1>

Min.: 0

Max.: B2

<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).

H1 Multi-Function Digital Input Selections

H1-

Setting

Function

LCD Display

Description

Page

0

3-Wire sequence

3-Wire Control

Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)

Terminals S1 and S2 are automatically set up for the Run command and Stop

command.

3

Multi-Step Speed

Reference 1

Multi-Step Ref 1

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

4

Multi-Step Speed

Reference 2

Multi-Step Ref 2

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

6

Jog reference selection

jog Freq Ref

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other

reference sources.

7

Accel/decel time

selection 1

Multi-Acc/Dec 1

Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel

time 2 (set in C1-03, C1-04).

8

Baseblock command

(N.O.)

Ext BaseBlk N.O.

Closed: No drive output

9

Baseblock command

(N.C.)

Ext BaseBlk N.C.

Open: No drive output

A

Accel/decel ramp hold

Acc/Dec RampHold

Open: Accel/decel is not held

Closed: The drive pauses during acceleration or deceleration and maintains the

output frequency.

B

Drive overheat alarm

(oH2)

OH2 Alarm Signal

Closed: Closes when an oH2 alarm occurs

C

Analog terminal input

selection

Term A2 Enable

Open: Function assigned by H3-14 is disabled.

Closed: Function assigned by H3-14 is enabled.