Output terminals, Serial communication terminals – Yaskawa Z1000 AC Drive HVAC User Manual

Page 87

Advertising
background image

n

Output Terminals

Table 3.5

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table 3.5 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Fault Relay

Output

MA

N.O. output (Fault)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

285

MB

N.C. output (Fault)

MC

Fault output common

Multi-Function
Digital Output

<1>

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

285

M2
M3

Multi-function digital output (Zero speed)

M4
M5

Multi-function digital output (Speed Agree 1)

M6

Monitor

Output

FM

Analog monitor output 1 (Output frequency)

0 to 10 V / 0 to 100%

4 to 20 mA / 0 to 100%

Voltage or current output must be selected by Jumper S5 and

H4-07 for FM and H4-08 for AM.

288

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

External Power

Supply

+P

External Power Supply

24 V (Max. 150 mA)

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 200,000 times (assumes 1 A, resistive load).

Connect a suppression diode as shown in

Figure 3.20

when driving a reactive load such as a relay coil. Ensure the diode rating

is greater than the circuit voltage.

A

B

C

D

A – External power, 48 V max.
B – Suppression diode

C – Coil
D – 50 mA or less

Figure 3.20 Connecting a Suppression Diode

n

Serial Communication Terminals

Table 3.6 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

Serial Communication

(APOGEE FLN,

BACnet, MEMOBUS/

Modbus, or Metasys
N2)

<1>

R+

Communications input (+)

APOGEE FLN, BACnet, MEMOBUS/

Modbus, or Metasys N2 communication: Use

an RS-422 or RS-485 cable to connect the

drive.

• APOGEE FLN

Comm. RS-422/

RS-485, 4.8 kbps

• BACnet Comm.

RS-485, max. 76.8

kbps

• MEMOBUS/

Modbus Comm.

RS-422/RS-485,

max. 115.2 kbps

• Metasys N2 Comm.

RS-422/RS-485, 9.6

kbps

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Communications ground

0 V

FE

Option card ground

<1> Enable the termination resistor in the last drive in an APOGEE FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 network by setting DIP switch

S2 to the ON position.

Refer to Control I/O Connections on page 92

for more information on the termination resistor.

3.9 Control Circuit Wiring

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

87

3

Electrical Installation

Advertising