Digital Operator Display

Fault Name

CPF22

Hybrid IC Failure

Cause

Possible Solution

Hybrid IC failure on the power board

• Cycle power to the drive.
• If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the power board.

Digital Operator Display

Fault Name

CPF23

Control Board Connection Error
Connection error between the control board and the drive

Cause

Possible Solution

Hardware is damaged

• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

CPF24

Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

CPF25

Terminal Board Not Connected

Cause

Possible Solution

Terminal board is not connected correctly

Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

Digital Operator Display

Fault Name

to
to

CPF26 to CPF35

CPF40 to CPF43

Control Circuit Error
CPU error

Cause

Possible Solution

Hardware is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

E5

MECHATROLINK Watchdog Timer Error
The watchdog timed out.

Cause

Possible Solution

Data has not been received from the PLC

Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and

proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.

Digital Operator Display

Fault Name

EF0

Option Card External Fault
An external fault condition is present.

Cause

Possible Solution

An external fault was received from the PLC

and F6-03 is set to a value other than 3.

• Remove the cause of the external fault.
• Remove the external fault input from the PLC.

Problem with the PLC program

Check the PLC program and correct problems.

Digital Operator Display

Fault Name

EF1

External Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External Fault (input terminal S2)
External fault at multi-function input terminal S2.

5.4 Fault Detection