D.3 ul and csa standards – Yaskawa Z1000 AC Drive HVAC User Manual

Page 345

Advertising
background image

Drive Model

Terminal

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0009

R/L1, S/L2, T/L3

2.5

(14)

2.5 to 6.0

(14 to 10)

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

2.5

(14)

2.5 to 6.0

(14 to 10)

⊖, ⊕1, ⊕2

2.5 to 6.0

(14 to 10)

B1, B2

2.5 to 6.0

(14 to 10)

6.0

(10)

4.0 to 6.0

(12 to 10)

5A0011

R/L1, S/L2, T/L3

6.0

(10)

2.5 to 16

(14 to 6)

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

2.5

(14)

2.5 to 16

(14 to 6)

⊖, ⊕1, ⊕2

2.5 to 16

(14 to 6)

B1, B2

2.5 to 6.0

(14 to 10)

10

(8)

4.0 to 6.0

(12 to 8)

M5

2.0 to 2.5

(17.7 to 22.1)

5A0017

R/L1, S/L2, T/L3

6.0

(10)

6.0 to 16

(10 to 6)

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

6.0

(10)

6.0 to 16

(10 to 6)

⊖, ⊕1, ⊕2

6.0 to 16

(10 to 6)

B1, B2

6.0 to 10

(10 to 8)

2.7 to 3.0

(23.9 to 26.6)

10

(8)

6.0 to 10

(12 to 8)

M6

5.4 to 6.0

(47.8 to 53.1)

5A0022

R/L1, S/L2, T/L3

10

(8)

6.0 to 16

(10 to 6)

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

6.0

(10)

6.0 to 16

(10 to 6)

⊖, ⊕1, ⊕2

6.0 to 16

(10 to 6)

B1, B2

6.0 to 10

(10 to 8)

2.7 to 3.0

(23.9 to 26.6)

10

(8)

6.0 to 10

(10 to 6)

M6

5.4 to 6.0

(47.8 to 53.1)

5A0027
5A0032

R/L1, S/L2, T/L3

16

(6)

16 to 25

(6 to 4)

M6

5.4 to 6.0

(47.8 to 53.1)

U/T1, V/T2, W/T3

16

(6)

16 to 25

(6 to 4)

⊖, ⊕1, ⊕2

16 to 25

(6 to 4)

B1, B2

6.0 to 10

(10 to 8)

M5

2.7 to 3.0

(23.9 to 26.6)

16

(6)

10 to 16

(10 to 6)

M6

5.4 to 6.0

(47.8 to 53.1)

5A0041

R/L1, S/L2, T/L3

16

(6)

6.0 to 25

(10 to 3)

M8

9.0 to 11

(79.7 to 97.4)

U/T1, V/T2, W/T3

16

(6)

6.0 to 25

(10 to 3)

⊖, ⊕1

(6 to 1)

B1, B2

4.0 to 25

(12 to 3)

16

(6)

10 to 16

(6)

D.3 UL and CSA Standards

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

345

D

Standards Compliance

Advertising