HOA Keypad Display

Error Name

Er-02

Minor Fault

Cause

Possible Solutions

An alarm was triggered during Auto-Tuning

Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and restart Auto-Tuning.

HOA Keypad Display

Error Name

Er-03

OFF Button Input

Cause

Possible Solutions

Auto-Tuning canceled by pressing the OFF button Auto-Tuning did not complete properly. Restart Auto-Tuning.

HOA Keypad Display

Error Name

Er-04

Line-to-Line Resistance Error

Cause

Possible Solutions

Motor data entered during Auto-Tuning was

incorrect

• Make sure motor data entered to T1- match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the

parameter setting range or the tuning process took

too long

Check and correct faulty motor wiring.

Faulty motor cable or cable connection

HOA Keypad Display

Error Name

Er-05

No-Load Current Error

Cause

Possible Solutions

Motor data entered during Auto-Tuning was

incorrect

• Make sure motor data entered to T1- match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the

parameter setting range or the tuning process took

too long

Check and correct faulty motor wiring.

HOA Keypad Display

Error Name

Er-08

Rated Slip Error

Cause

Possible Solutions

Motor data entered during Auto-Tuning was

incorrect

• Make sure motor data entered to T1- match motor nameplate information.
• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the

parameter setting range or the tuning process took

too long

Check and correct faulty motor wiring.

HOA Keypad Display

Error Name

Er-09

Acceleration Error

Cause

Possible Solutions

The motor did not accelerate for the specified

acceleration time

• Increase the acceleration time (C1-01).
• Disconnect the machine from the motor if possible.

HOA Keypad Display

Error Name

Er-12

Current Detection Error

Cause

Possible Solutions

One of the motor phases is missing:

(U/T1, V/T2, W/T3)

Check motor wiring and correct any problems.

The current exceeded the current rating of the drive • Check motor wiring for a short between motor lines.

• Close any magnetic contactors used between motors.
• Replace the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or your nearest sales representative.

The current is too low

Attempted Auto-Tuning without motor connected

to the drive

Connect the motor and restart Auto-Tuning.

Current detection signal error

Replace the control board or the entire drive. For instructions on replacing the control board, contact