Wiring the control circuit terminal, Ends. refer to, Table 3.8 – Yaskawa Z1000 AC Drive HVAC User Manual

Page 89: For ferrule terminal types and sizes

Advertising
background image

n

Ferrule-Type Wire Terminals

Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends

with insulated sleeves before connecting to the drive. See

Table 3.8

for dimensions.

d1

d2

8 mm

L

Figure 3.22 Ferrule Dimensions

Table 3.8 Ferrule Terminal Types and Sizes

Size mm

2

(AWG)

Type

L (mm)

d1 (mm)

d2 (mm)

Manufacturer

0.25 (24)

AI 0.25-8YE

12.5

0.8

1.8

PHOENIX CONTACT

0.34 (22)

AI 0.34-8TQ

10.5

0.8

1.8

0.5 (20)

AI 0.5-8WH or

AI 0.5-8OG

14

1.1

2.5

u

Wiring the Control Circuit Terminal

This section describes the proper procedures and preparations for wiring the control terminals.

WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result

in death or serious injury.

NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3,

, 1, 2) and

other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.

NOTICE: Separate wiring for digital output terminals MA, MB, MC, and M1 to M6 from wiring to other control circuit lines. Improper wiring

practices could result in drive or equipment malfunction or nuisance trips.

NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in

drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,

Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.

NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could

result in drive or equipment malfunction due to short circuit.

NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or

equipment malfunction or nuisance trips.

NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to the

terminal block, or cause a fire.

NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or

equipment malfunction due to electrical interference.

Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete.

Refer to

Terminal Board Wiring Guide on page 90

for details. Prepare the ends of control circuit wiring as shown in

Figure 3.25

.

Connect control wires as shown in

Figure 3.23

and

Figure 3.24

.

3.9 Control Circuit Wiring

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

89

3

Electrical Installation