Single Drive Installation

Figure 2.2

shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink

against a closed surface to avoid diverting cooling air around the heatsink.

A

A

B

B

Side Clearance

Top/Bottom Clearance

C

C

D

D

A – 50 mm minimum
B – 30 mm minimum

C – 120 mm minimum
D – Airflow direction

Figure 2.2 Correct Installation Spacing

Note:

IP20/NEMA Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for

installation.

n

Multiple Drive Installation (Side-by-Side Installation)

Models 5A0003 to 5A0032 can take advantage of Side-by-Side installation.
When installing multiple drives into the same enclosure panel, mount the drives according to

Figure 2.2

and set L8-35,

Installation Method Selection, to 1 (Side-by-Side Mounting).
When mounting drives with the minimum clearance of 2 mm according to

Figure 2.3

, set parameter L8-35 to 1 while

considering derating.

Refer to Parameter List on page 261

for details.

A

A

A

A

B

C

B

Side Clearance

Line up the tops of the drives.

D

D

Top/Bottom Clearance

A – 50 mm minimum
B – 30 mm minimum

C – 2 mm minimum
D – 120 mm minimum

Figure 2.3 Space Between Drives (Side-by-Side Mounting)

Note:

Align the tops of the drives when installing drives of different heights in the same enclosure panel. Leave space between the tops and bottoms

of stacked drives for easier cooling fan replacement.