Single drive installation, 2 mechanical installation – Yaskawa Z1000 AC Drive HVAC User Manual
Page 39
n
Single Drive Installation
against a closed surface to avoid diverting cooling air around the heatsink.
A
A
B
B
Side Clearance
Top/Bottom Clearance
C
C
D
D
A – 50 mm minimum
B – 30 mm minimum
C – 120 mm minimum
D – Airflow direction
Figure 2.2 Correct Installation Spacing
Note:
IP20/NEMA Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for
installation.
n
Multiple Drive Installation (Side-by-Side Installation)
Models 5A0003 to 5A0032 can take advantage of Side-by-Side installation.
When installing multiple drives into the same enclosure panel, mount the drives according to
and set L8-35,
Installation Method Selection, to 1 (Side-by-Side Mounting).
When mounting drives with the minimum clearance of 2 mm according to
, set parameter L8-35 to 1 while
Refer to Parameter List on page 261
A
A
A
A
B
C
B
Side Clearance
Line up the tops of the drives.
D
D
Top/Bottom Clearance
A – 50 mm minimum
B – 30 mm minimum
C – 2 mm minimum
D – 120 mm minimum
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Note:
Align the tops of the drives when installing drives of different heights in the same enclosure panel. Leave space between the tops and bottoms
of stacked drives for easier cooling fan replacement.
2.2 Mechanical Installation