Setting 0: Forward
Setting 1: Reverse

n

o3-01: Copy Function Selection

Instructs the drive to Read, Write, or Verify parameter settings.

No.

Name

Setting Range

Default

o3-01

Copy Function Selection

0 to 3

0

Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ

Copies all parameters from the drive to the HOA keypad.

Note:

The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.

Setting 2: OP --> INV WRITE

Copies all parameters from the HOA keypad to the drive.

Setting 3: OP<-->INV VERIFY

Compares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.

n

o3-02: Copy Allowed Selection

Allows and restricts the use of the Copy function.

No.

Name

Setting Range

Default

o3-02

Copy Allowed Selection

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

n

o4-01: Cumulative Operation Time Setting

Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of

operation time from some desired value. Total operation time can be viewed in monitor U4-01.

Note:

The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also

be displayed in monitor U4-01.

No.

Name

Setting Range

Default

o4-01

Cumulative Operation Time Setting

0 to 9999 h

0 h

n

o4-02: Cumulative Operation Time Selection

Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.

No.

Name

Setting Range

Default

o4-02

Cumulative Operation Time Selection

0, 1

1

Setting 0: Power on Time

The drive logs the time it is connected to a power supply, regardless of whether the motor is running.

Setting 1: Run Time

The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)

and when there is voltage output.

n

o4-03: Cooling Fan Operation Time Setting

Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03

also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after

replacing the cooling fan.

Note:

1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”

will be displayed in monitor U4-03.

2. The cooling fan may require maintenance at an earlier date in harsher environments.

No.

Name

Setting Range

Default

o4-03

Cooling Fan Operation Time Setting

0 to 9999 h

0 h