Yaskawa Z1000 AC Drive HVAC User Manual

Page 325

Advertising
background image

n

H5-14, H5-15: BACnet Device Object Identifiers 0 and 1

These parameters set the Instance Identifier of the BACnet Device Object, where the H5-14 value is the least significant word

and the H5-15 value is the most significant word.

No.

Name

Setting Range

Default

H5-14

BACnet Device Object Identifier 0

0 to FFFFH

1

H5-15

BACnet Device Object Identifier 1

0 to 3FH

0

Example 1: Set Device Object Instance Identifier of “1234”
1234 decimal is equal to 4D2H (hexadecimal)
Set H5-14 to 4D2H and set H5-15 to 0.
Example 2: Set Device Object Instance Identifier of “1234567”
12334567 decimal is equal to 12D687H
Set H5-14 to D687H and set H5-15 to 12H.

C.4 BACnet Setup Parameters

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

325

C

BACnet Communications