Yaskawa Z1000 AC Drive HVAC User Manual
Page 277
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E5-09
(331)
Motor Induction Voltage
Constant 1
PM Mtr Ind V 1
OLV/PM
OLV/PM
Sets the induced peak voltage per phase in units of
0.1 mV/(rad/s) [electrical angle]. Set this parameter when using
an IPM motor with variable torque.
Set E5-24 to 0 when setting this parameter.
Default:
<1>
Min.: 0.0 mV/
(rad/s)
Max.: 2000.0
mV/
(rad/s)
E5-24
(353)
Motor Induction Voltage
Constant 2
PM Mtr Ind V 2
OLV/PM
OLV/PM
Sets the induced phase-to-phase rms voltage in units of
0.1 mV/(r/min) [mechanical angle].
Default:
<1>
Min.: 0.0 mV/
(r/min)
Max.: 6500.0
mV/
(r/min)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
B.5 E: Motor Parameters
YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual
277
B
Parameter List