Yaskawa Z1000 AC Drive HVAC User Manual

Page 171

Advertising
background image

Setting F: Through Mode

When set to F, an input does not affect any drive function, but the input level can still be read out by a PLC via APOGEE

FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 communications.

Setting 16: Differential PI Feedback

If an analog value is set for this function, the PI controller is set for differential feedback. The difference of the PI feedback

input value and the differential feedback input value builds the feedback value used to calculate the PI input.

n

H5-01: Drive Slave Address

Sets the drive slave address used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-01

Drive Slave Address

0 to FFH

1FH

Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to

be assigned in sequential order, but no two drives may share the same address.

n

H5-02: Communication Speed Selection

Sets the communications speed for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2.

Note:

1. Cycle the power after changing this parameter to enable the new setting.
2. When Metasys N2 communications are selected (H5-08 = 1), selecting a baud rate other than 9600 bps will trigger an oPE29 error.
3. When APOGEE FLN (P1) communications are selected (H5-08 = 2), selecting a baud rate other than 4800 bps will trigger an oPE29

error.

4. When BACnet communications are selected (H5-08 = 3), selecting 115200 bps (Setting 8) will trigger an oPE29 error.

No.

Name

Setting Range

Default

H5-02

Communication Speed Selection

0 to 8

<1>

<1> Default depends on H5-08 setting:

H5-08 = 0, MEMOBUS/Modbus; default: 3
H5-08 = 1, N2 (Metasys); default: 3
H5-08 = 2, P1 (APOGEE FLN); default: 2
H5-08 = 3, BACnet; default: 3

H5-02

Communication Speed

H5-02

Communication Speed

0

<1>

1200 bps

5

<1>

38400 bps

1

<1>

2400 bps

6

<1>

57600 bps

2

4800 bps

7

<1>

76800 bps

3

<1>

9600 bps

8

<1> <2>

115200 bps

4

<1>

19200 bps

<1> Not available when H5-08 is set to 2 P1 (APOGEE FLN).
<2> Not available when H5-08 is set to 0 (MEMOBUS/Modbus) or 1 (Metasys N2).

n

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

171