S3: secondary pi (pi2) control – Yaskawa Z1000 AC Drive HVAC User Manual

Page 303

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S2-17

(3216)

Sequence Timer 4 Stop

Time

Tmr 4 Stop Time

Sets the stop time for timer 4. The value must be set greater than

or equal to S2-16.

Default: 00:00

Min.: 00:00

Max.: 24:00

S2-18

(3217)

Sequence Timer 4 Day

Selection

Tmr 4 Day Sel

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Sets the days for which sequence timer 4 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-19

(3218)

Sequence Timer 4

Selection

Tmr 4 Seq Sel

0: Digital out only

1: Run

2: Run - PI Disable

Sets the action that occurs when sequence timer 4 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

S2-20

(3219)

Sequence Timer 4

Reference Source

Tmr 4 Ref Source

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial com

6: Option PCB

Selects the frequency reference source used for running the drive

when sequence timer 4 is active (only applicable when S2-19 is

set to 1 or 2).

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial communication

6: Option card

Default: 0

Range: 0 to 6

u

S3: Secondary PI (PI2) Control

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S3-01

(321A) Secondary PI Enable

Selection

PI2 Enable Sel

0: Disabled

1: Always

2: Drive running

3: Motor running

0: Secondary PI disabled

1: Always

2: Drive running

3: Motor running

Default: 0

Range: 0 to 3

S3-02

(321B) Secondary PI User

Display

PI2 UsrDspMaxVal

Sets the scale value of 100% PI input.

Default: 10000

Min.: 0

Max.: 60000

S3-03

(321C) Secondary PI Display

Digits

PI2 UsrDspDigits

0: No Dec (XXXXX)

1: 1 Dec (XXXX.X)

2. 2 Dec (XXX.XX)

3: 3 Dec (XX.XXX)

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 2

Range: 0 to 3

S3-04

(321D) Secondary PI Unit

Selection

PI2 Unit Sel

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: LPM

13: CMM

14: No unit

15: %

0: Inch of water (WC)

1: Pounds per square inch (PSI)

2: Gallons per minute (GPM)

3: Degrees Fahrenheit (F)

4: Cubic feet per minute (CFM)

5: Cubic meters per hour (CMH)

6: Liters per hour (LPH)

7: Liters per second (LPS)

8: Bar (Bar)

9: Pascals (Pa)

10: Degrees Celsius (C)

11: Meters (Mtr) (Ft: Feet)

12: Liters per minute (LPM)

13: Cubic meters per minute (CMM)

14: No unit

15: Percentage (%)

Default: 15

Range: 0 to 15

B.11 S: Special Application

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

303

B

Parameter List

Advertising