Binary output objects, Binary value objects – Yaskawa Z1000 AC Drive HVAC User Manual

Page 331

Advertising
background image

u

Binary Output Objects

Table C.9 Binary Output Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BO1

MF Output M1-M2

0009H:bit 0

ON

OFF

C

BO2

MF Output M3-M4

0009H:bit 1

ON

OFF

C

BO3

MF Output MA-MC

0009H:bit 2

ON

OFF

C

BO4

Ref Sel: PI Setpoint

000FH:bit 1

ON

OFF

C

BO5

Ref Sel: Term S5 IN

000FH:bit 12

ON

OFF

C

BO6

Ref Sel: Term S6 IN

000FH:bit 13

ON

OFF

C

BO7

Refl Sel: Term S7 IN

000FH:bit 14

ON

OFF

C

u

Binary Value Objects

Table C.10 Binary Value Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV1

RUN FWD

0001H:bit 0

RUN

OFF

C

BV2

RUN REV

0001H:bit 1

REV

OFF

C

BV3

EXT FAULT

0001H:bit 2

FAULT

OFF

C

BV4

FAULT RESET

0001H:bit 3

RESET

OFF

C

BV5

COM NET

0001H:bit 4

COM

LOCAL

C

BV6

COM CNTRL

0001H:bit 5

COM

LOCAL

C

BV7

MF Input 3 Cmd

0001H:bit 6

ON

OFF

C

BV8

MF Input 4 Cmd

0001H:bit 7

ON

OFF

C

BV9

MF Input 5 Cmd

0001H:bit 8

ON

OFF

C

BV10

MF Input 6 Cmd

0001H:bit 9

ON

OFF

C

BV11

MF Input 7 Cmd

0001H:bit 10

ON

OFF

C

BV12

Set Fault Contact Cmd

0009H:bit 6

ENABLE

OFF

C

BV13

RUN-STOP

0020H:bit 0

RUN

OFF

R

BV14

REV-FWD

0020H:bit 1

REV

FWD

R

BV15

READY

0020H:bit 2

READY

OFF

R

BV16

FAULT

0020H:bit 3

FAULTED

OFF

R

BV17

Data Set Error

0020H:bit 4

ERROR

OFF

R

BV18

Overcurrent – Ground Fault

0021H:bit 0

OC-GF

OFF

R

BV19

Main Circuit Overvoltage

0021H:bit 1

OV

OFF

R

BV20

Drive Overload

0021H:bit 2

OL2

OFF

R

BV21

Drive Overheat

0021H:bit 3

OH1-OH2

OFF

R

BV22

Fuse Blown

0021H:bit 5

PUF

OFF

R

BV23

PI Feedback Loss

0021H:bit 6

FBL

OFF

R

BV24

External Fault

0021H:bit 7

EF0-EF

OFF

R

BV25

Hardware Error

0021H:bit 8

CPF

OFF

R

BV26

Mtr Ovrld-OvrTorque

0021H:bit 9

OL1-OL3

OFF

R

BV27

Overspeed

0021H:bit 10

OS-DEV

OFF

R

BV28

Main CKT Undervoltage

0021H:bit 11

UV

OFF

R

BV29

MCU, Cntl Pwr Sy Err

0021H:bit 12

UV1-2-3

OFF

R

BV30

Output Phase Loss

0021H:bit 13

LF

OFF

R

BV31

Communication Error

0021H:bit 14

CE

OFF

R

BV32

Operator Disconnect

0021H:bit 15

OPR

OFF

R

BV33

Operating

002CH:bit 0

OPERATING

OFF

R

BV34

Aero Speed

002CH:bit 1

ON

OFF

R

C.7 BACnet Objects Supported

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

331

C

BACnet Communications

Advertising