Analog input objects, Analog output objects, Analog value objects – Yaskawa Z1000 AC Drive HVAC User Manual

Page 329

Advertising
background image

Property

Object Type

Device

Analog

Input

Analog

Output

Analog

Value

Binary

Output

Binary

Output

Binary

Value

Inactive_Text

Yes

Yes

Yes

Active_Text

Yes

Yes

Yes

<1> For Commandable Object Instances only.

u

Analog Input Objects

Table C.5 Analog Input Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AI1

Analog Input 1 Level

004EH

XXXX.X

%

R

AI2

Analog Input 2 Level

004FH

XXXX.X

%

R

AI3

Not used

AI4

Not used

AI5

Not used

AI6

Display Format o1-03

0502H

XXXXX

R

AI7

Scale Format b5-20

01E2H

XXXXX

R

AI8

Inverter Model o2-04

0508F

XXXXX

R

AI9

Rated Current n9-01

05D0H

XXXX.X

Amps

R

u

Analog Output Objects

Table C.6 Analog Output Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AO1

Analog Output 1 Level

0007H

XXXX.X

0 to 100.0

%

C

AO2

Analog Output 2 Level

0008H

XXXX.X

0 to 100.0

%

C

u

Analog Value Objects

Table C.7 Analog Value Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AV1

Not used

AV2

Frequency Command

0002H

XXX.XX

Depends on

o1-03

0.00 to 600.00

Hz

Depends on

o1-03

C

AV3

PI Setpoint

0006H

XXX.XX

0.00 to 100.00

%

C

AV4

Not used

AV5

Not used

AV6

Not used

AV7

Not used

AV8

Not used

AV9

Frequency Reference

0040H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV10

Output Frequency

0041H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV11

Output Voltage

0045H

XXXX.X

Volts

R

C.7 BACnet Objects Supported

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

329

C

BACnet Communications

Advertising