D: references, D1: frequency reference, D2: frequency upper/lower limits – Yaskawa Z1000 AC Drive HVAC User Manual

Page 272: B.4 d: references

Advertising
background image

B.4 d: References

Reference parameters set the various frequency reference values during operation.

u

d1: Frequency Reference

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

d1-01

(280)

Frequency Reference 1 Reference 1

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

164

d1-02

(281)

Frequency Reference 2 Reference 2

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

164

d1-03

(282)

Frequency Reference 3 Reference 3

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

164

d1-04

(283)

Frequency Reference 4 Reference 4

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

164

d1-16

(291)

Frequency Reference 16 Reference 16

Sets the frequency reference for the drive. Setting units are

determined by parameter o1-03.

Default: 0.00 Hz

Min.: 0.00
Max.: 240.00

<1>

164

d1-17

(292)

Jog Frequency

Reference

Jog Reference

Sets the Jog frequency reference. Setting units are determined

by parameter o1-03.

Default: 6.00 Hz

Min.: 0.00
Max.: 240.0

<1>

164

<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.

u

d2: Frequency Upper/Lower Limits

No.

(Addr.

Hex.)

Name

LCD Display

Description

Setting

Page

d2-01

(289)

Frequency Reference

Upper Limit

Ref Upper Limit

Sets the frequency reference upper limit as a percentage of the

maximum output frequency.

Default: 100.0%

Min.: 0.0

Max.: 110.0

127

d2-02

(28A)

Frequency Reference

Lower Limit

Ref Lower Limit

Sets the frequency reference lower limit as a percentage of the

maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

127

d2-03

(293)

Master Speed Reference

Lower Limit

Ref1 Lower Limit

Sets the lower limit for frequency references from analog inputs

as a percentage of the maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

165

B.4 d: References

272

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual