n8: PM Motor Control Tuning

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

n8-45

(538)

Speed Feedback

Detection Control Gain PM Spd Fdbk Gain

OLV/PM

OLV/PM

Increase this setting if hunting occurs. Decrease to lower the

response.

Default: 0.80

Min.: 0.00

Max.: 10.00

n8-47

(53A)

Pull-In Current

Compensation Time

Constant

PM Pull-in I Tc

OLV/PM

OLV/PM

Sets the time constant to make the pull-in current reference and

actual current value agree. Decrease the value if the motor

begins to oscillate, and increase the value if it takes too long for

the current reference to equal the output current.

Default: 5.0 s

Min.: 0.0

Max.: 100.0

n8-48

(53B)

Pull-In Current

PM No-load Curr

OLV/PM

OLV/PM

Defines the d-Axis current reference during no-load operation

at a constant speed. Set as a percentage of the motor rated

current. Increase this setting if hunting occurs while running at

constant speed.

Default: 30%

Min.: 20

Max.: 200

n8-49

(53C)

d-Axis Current for High

Efficiency Control

EnergySav ID Lvl

OLV/PM

OLV/PM

Sets the d-Axis current reference when running a high load at

constant speed. Set as a percentage of the motor rated current.

Default:

<1>

Min.: -200.0%

Max.: 0.0%

n8-51

(53E)

Acceleration/

Deceleration Pull-In

Current

PM Pull-in I@Acc

OLV/PM

OLV/PM

Sets the d-Axis current reference during acceleration/

deceleration as a percentage of the motor rated current. Set to a

high value when more starting torque is needed.

Default: 50%

Min.: 0

Max.: 200

n8-54

(56D)

Voltage Error

Compensation Time

Constant

PM V Error CompT

OLV/PM

OLV/PM

Adjusts the value when hunting occurs at low speed. If hunting

occurs with sudden load changes, increase n8-54 in increments

of 0.1. Reduce this setting if oscillation occurs at start.

Default: 1.00 s

Min.: 0.00

Max.: 10.00

n8-55

(56E)

Load Inertia

PMLoad wk2 Ratio

0: Less than 1:10

1: 1:10 to 1:30

2: 1:30 to 1:50

3: More than 1:50

OLV/PM

OLV/PM

Sets the ratio between motor and machine inertia.

0: Lower than 1:10

1: Between 1:10 to 1:30

2: Between 1:30 to 1:50

3: Higher than 1:50

Default: 0

Min.: 0

Max.: 3

n8-62

(57D)

Output Voltage Limit

PM Vout Limit

OLV/PM

OLV/PM

Prevents output voltage saturation. Should be set just below the

voltage provided by the input power supply.

Default: 575.0 V

Min.: 0.0

Max.: 661.3

n8-65

(65C)

Speed Feedback

Detection Control Gain

during ov Suppression

SFdbk G @OV Supp

OLV/PM

OLV/PM

Sets the gain used for internal speed feedback detection during

ov suppression.

Default: 1.50

Min.: 0.00

Max.: 10.00

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

B.9 n: Special Adjustment

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

297