Setting 0: Reverse Disabled

Negative PI output will be limited to zero and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PI output will cause the drive to run in the opposite direction.

n

C2-01 and C2-02: S-Curve Characteristics

C2-01 and C2-02 set separate S-curves for each section of the acceleration or deceleration.

No.

Parameter Name

Setting Range

Default

C2-01

S-Curve Characteristic at Accel Start

0.00 to 10.00 s

Determined by

A1-02

C2-02

S-Curve Characteristic at Accel End

0.20 s

Figure 4.30

illustrates S-curve application.

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

FWD run

REV run

Output
frequency

<1> S-Curve characteristic at Decel Start/End is fixed to 0.20 s.

Figure 4.30 S-Curve Timing Diagram - FWD/REV Operation

Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2

n

C6-03, C6-04, C6-05: Carrier Frequency Upper Limit, Lower Limit, Proportional Gain

Note:

C6-04 and C6-05 are available in V/f Control mode only.

These parameters set a user-defined or a variable carrier frequency. Set C6-02 to F to set the upper and lower limits and the

carrier frequency proportional gain.

No.

Parameter Name

Setting Range

Default

C6-03

Carrier Frequency Upper Limit

1.0 to 15.0 kHz

Determined by

C6-02

C6-04

Carrier Frequency Lower Limit (V/f Control only)

1.0 to 15.0 kHz

C6-05

Carrier Frequency Proportional Gain (V/f Control only)

0 to 99

Setting a Fixed User-Defined Carrier Frequency

A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to F.

In V/f Control, adjust parameter C6-04 to the same value as C6-03.

Setting a Variable Carrier Frequency (V/f Control)

In V/f Control, the carrier frequency can be set up to change linearly with the output frequency by setting the upper and lower

limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) as shown in

Figure 4.31

.