L4: speed detection, L5: fault restart – Yaskawa Z1000 AC Drive HVAC User Manual

Page 293

Advertising
background image

u

L4: Speed Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-01

(499)

Speed Agreement

Detection Level

Spd Agree Level

L4-01 sets the frequency detection level for digital output

functions H2- = 2, 3, 4, 5.

Default: 0.0 Hz

Min.: 0.0

Max.: 240.0

L4-02

(49A)

Speed Agreement

Detection Width

Spd Agree Width

L4-02 sets the hysteresis or allowable margin for speed

detection.

Default:2.0 Hz

Min.: 0.0

Max.: 20.0

L4-03

(49B)

Speed Agreement

Detection Level (+/-) Spd Agree Lvl+-

L4-03 sets the frequency detection level for digital output

functions H2- = 13, 14, 15, 16.

Default: 0.0 Hz

Min.: -240.0

Max.: 240.0

L4-04

(49C)

Speed Agreement

Detection Width

(+/-)

Spd Agree Wdth+-

L4-04 sets the hysteresis or allowable margin for speed

detection.

Default: 2.0 kHz

Min.: 0.0

Max.: 20.0

L4-05

(49D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1: Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 1

Range: 0, 1

132

L4-06

(4C2)

Frequency Reference

at Reference Loss

Fref at Floss

Sets the percentage of the frequency reference that the drive

should run with when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

132

L4-07

(470)

Speed Agreement

Detection Selection

Freq Detect Sel

0: No Detection @BB

1: Always Detected

0: No detection during baseblock.

1: Detection always enabled.

Default: 0

Range: 0, 1

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(49E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,

STo, Uv1.

Default: 0

Min.: 0

Max.: 10

132

L5-02

(49F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

173

L5-03

(4A0)

Time to Continue

Making Fault Restarts

Max Restart Time

Enabled only when L5-05 is set to 0. Causes a fault if a fault

restart cannot occur after the set time passes.

Default: 180.0 s

Min.: 0.0

Max.: 600.0

132

L5-04

(46C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 10.0 s

Min.: 0.5

Max.: 600.0

173

L5-05

(467)

Fault Reset Operation

Selection

Fault Reset Sel

0: Continuous

1: Use L5-04 Time

0: Continuously attempt to restart while incrementing restart

counter only at a successful restart (same as F7 and G7).

1: Attempt to restart with the interval time set in L5-04 and

increment the restart counter with each attempt (same as V7).

Default: 1

Range: 0, 1

174

B.8 L: Protection Function

YASKAWA ELECTRIC TOEP YAIZ1U 03A YASKAWA AC Drive – Z1000 User Manual

293

B

Parameter List

Advertising