Touch-screen interface, Lcd display module, Relay board – Teledyne 6200T - Sulfides Analyzer User Manual

Page 253

Advertising
background image

6200T Total Sulfur Analyzer

Troubleshooting

Teledyen Analytical Instruments

253

12.6.4. Touch-screen Interface

Verify the functioning of the touch screen by observing the display when pressing a
touch-screen control button. Assuming that there are no wiring problems and that the
DC power supplies are operating properly, but pressing a control button on the touch
screen does not change the display, any of the following may be the problem:

 The touch-screen controller may be malfunctioning.
 The internal USB bus may be malfunctioning.

You can verify this failure by logging on to the instrument using AICOM or a terminal
program. If the analyzer responds to remote commands and the display changes
accordingly, the touch-screen interface may be faulty.

12.6.5. LCD Display Module

Verify the functioning of the front panel display by observing it when power is applied
to the instrument. Assuming that there are no wiring problems and that the DC power
supplies are operating properly, the display screen should light and show the splash
screen and other indications of its state as the CPU goes through its initialization
process.

12.6.6. Relay Board

The relay board circuit can most easily be checked by observing the condition of its
status LEDs as described in Section 12.2, and the associated output when toggled on and
off through the SIGNAL I/O function in the DIAG menu, refer to Section 5.9.1.

 If the front panel display responds to button presses and D1 on the relay

board is not flashing, then either the I

2

C connection between the

motherboard and the relay board is bad, or the relay board itself is bad.

 If D1 on the relay board is flashing, but toggling an output in the Signal I/O

function menu does not toggle the output’s status LED, the there is a circuit
problem, or possibly a blown driver chip, on the relay board.

 If D1 on the Relay board is flashing and the status indicator for the output

in question (heater, valve, etc.) toggles properly using the Signal I/O
function, but the output device does not turn on/off, then the associated
device (valve or heater) or its control device (valve driver, heater relay) is
malfunctioning.

Several of the control devices are in sockets and can easily be replaced. The table below
lists the control device associated with a particular function:

Table 12-6: Relay Board Control Devices

FUNCTION CONTROL

DEVICE

SOCKETED

Valve0 – Valve3

U5

Yes

Valve4 – Valve7

U6

Yes

All heaters

K1-K5

Yes

Advertising