Part 1 Specification

Chapter 3 Gateway R unit

84

Part 1 Specification

(6) Home Return Command (HOME) PLC Output Signal

Home Return Complete (HEND) PLC Input Signal

Home return operation will start at the “0” (OFF) Æ “1” (ON) leading edge of the HOME signal.

When home return is complete, the HEND (home return complete) signal will turn “1” (ON).

Turn the HOME signal “0” (OFF) after the HEND signal has turned “1” (ON). Once it turns “1,” the HEND signal will not

turn “0” (OFF) until the power is turned OFF or the HOME signal is input again. After home return has been completed

once, home return can be performed as many times as desired using the HOME signal.

An absolute reset must be performed for each axis (controller unit) connected to a simple absolute R unit, when the

system is started.

To perform an absolute reset from the host PLC, output the home return signal (HOME).

For details, refer to the section on starting up the simple absolute R unit in Part 2, “Startup.”

Caution

1. If a positioning command is issued in the positioner mode immediately after the power has been turned ON, without

performing home return, home return will be performed automatically, but only if no home return has been performed

after the power ON, and then the positioning will be executed.

2. Take note that in any other mode, an alarm “Error 83: ALARM HOME ABS (absolute position move command before

home return)” will generate.

Actuator operation

Mechanical end

Stops at the home position

-106-

Advertising