Part 1 Specification

Chapter 3 Gateway R unit

88

Part 1 Specification

(14) Jog+ Command/Jog- Command (JOG+/JOG-) PLC Output Signal

These signals function as start commands for jogging operation or inching operation.

The + command starts operation in the direction opposite home, while the – command starts operation in the home

direction.

Jogging operation or inching operation is specified by a combination of this signal and the JISL signal (jogging/inching

switching signal) and JVEL signal (jogging/inching speed and inching distance parameter switching signal).

[1] Jogging operation

The actuator can be jogged when the jogging/inching switching signal (JISL) is “0” (OFF).

The actuator will operate in the direction opposite home while the JOG+ is “1” (ON), and decelerate to a stop when

the signal turns “0” (OFF).

The actuator will operate in the direction of home while the JOG- is “1” (ON), and decelerate to a stop when the

signal turns “0” (OFF).

The operation is set by the following parameters:

x

Speed:

Jogging speed in the parameter specified by the jogging speed/inching distance

switching (JVEL) signal

JVEL signal = “0” (OFF)o Parameter No. 26 (PIO jogging speed)

JVEL signal = “1” (ON)o Parameter No. 47 (PIO jogging speed 2)

x

Acceleration/deceleration: Rated acceleration/deceleration (The specific value varies depending on the actuator.)

To stop the jogging operation (cause the actuator to decelerate to a stop), change the active JOG signal from “1”

(ON) to “0” (OFF) or turn both the JOG+ and JOG- “1” (ON).

[2] Inching operation

The actuator can be inched when the jogging/inching switching signal (JISL) is “1” (ON).

The actuator moves by the inching distance every time the JOG signal changes from “0” (OFF) to “1” (ON).

The JOG+ signal causes the actuator to inch in the direction opposite home, while the JOG- signal causes the

actuator to inch in the direction of home.

The operation is set by the following parameters:

x

Speed:

Jogging speed set in the parameter specified by the JVEL signal

JVEL signal = “0” (OFF)o Parameter No. 26 (PIO jogging speed)

JVEL signal = “1” (ON)o Parameter No. 47 (PIO jogging speed 2)

x

Travel distance:

Travel distance set in the parameter specified by the JVEL signal

JVEL signal = “0” (OFF)o Parameter No. 48 (PIO inching distance)

JVEL signal = “1” (ON)o Parameter No. 49 (PIO inching distance 2)

x

Acceleration/deceleration: Rated acceleration/deceleration (The specific value varies depending on the actuator.)

Normally while the actuator is operating, the actuator will continue to operate even when the JOG+ or JOG- signal is

turned “1” (ON) (= the JOG signal will be ignored). Also while the actuator is paused,

turning the JOG+ or JOG- signal “1” (ON) will not cause the actuator to operate (= the

JOG signal will be ignored).

Caution

Exercise caution that until home return is completed, the software stroke limits are ineffective and therefore the actuator

may collide with a mechanical end.