Part 1 Specification

Chapter 3 Gateway R unit

118

Part 1 Specification

3.9 Modbus Gateway Mode of RS485 SIO

3.9.1 Overview

With the RS485 SIO Gateway R unit, the Modbus gateway mode in which the unit operates as a Modbus/RTU slave station,

and the SIO through mode in which the unit operates by means of serial communication per the Modbus/RTU and ASCII

protocols, are available.

For the operation in the SIO through mode, refer to the operation manual “ROBO CYLINDER Series – Serial Communication

(Modbus Version).”

This section explains the Modbus gateway mode.

Modbus/RTU is the only applicable communication protocol in this mode, and the unit must be connected to a serial port that

supports the Modbus/RTU protocol.

Axes are operated by sending communication messages under the Modbus/RTU protocol to the Gateway R unit (RGW-SIO)

and accessing the gateway’s registers (addresses F600 onward and F700 onward in the PLC).

Normally communication messages must be created using a PLC ladder sequence. If the number of communications

increases, however, the required ladder sequence will become large and complex and creating an appropriate sequence will

require a longer time.

Accordingly, the “Modbus cyclic communication FBL” is provided as a dedicated communication function block. This function

block is very useful because the user can use it to create a ladder sequence without a need to consider serial communication.

To use this function block, the PLC must meet the following conditions:

[1] CPU unit

CS/CJ Series by Omron

(If the function block is to be used, the CS/CJ Series unit must be Version 4.0 or later.)

[2] Serial communication unit CS/CJ Series by Omron

CS: CS1W-SCU**-V1 (Version 1.2 or later)

CJ: CS1W-SCU**-V1 (Version 1.2 or later)

[3] CX Programmer

Version 7.0 or later

Caution

Switch between the Modbus gateway mode and SIO through mode using the user setting switch (SW2) on the Gateway R

unit.

SW2 ON: SIO through mode

OFF: Modbus gateway mode