Recommended Emergency Stop Circuit

Shown below is an example of an emergency stop circuit of a ROBONET system.

The built-in drive-source cutoff relays of all axis controller units are turned ON/OFF simultaneously using the emergency stop

switch of the emergency stop circuit or teaching pendant connected to the Gateway R unit.

Caution

If an emergency stop is actuated with the emergency stop button, the emergency stop can be reset using the emergency

stop reset switch. If an emergency stop is actuated with a teaching pendant, however, the emergency switch will be reset

when the same emergency switch is turned and reset.

EMG connector

TP connector

Teaching pendant

Gateway R unit

Axis controller unit

Axis controller unit

ROBONET Communication Connector

TP connection

detection circuit

Drive-source cutoff signal

(CPU control signal)

Motor drive source

Motor drive source

Drive-source cutoff relay

Drive-source cutoff relay

Power-supply input terminal block

Internal power supply

common GND

Emergency

stop reset Emergency stop