Part 1 Specification

Chapter 3 Gateway R unit

174

Part 1 Specification

The function block parameters are used to specify the following addresses of the PLC’s I/O memory to be linked with the

gateway unit’s memory areas:

x

Initial gateway control signal address

x

Initial request command area address

x

Initial axis data specification area address

x

Initial gateway status signal address

x

Initial response command area address

x

Initial axis status area address

The PLC’s I/O memory areas that can be set by parameters include W (internal auxiliary relays), D (data memory), A

(special auxiliary relays), E (extended data memory), H (holding relays), and CIO (channel I/Os).

The function block is able to exchange data between the specified I/O memory areas and the gateway unit’s memory

areas linked to these I/O memory areas, via serial communication.

The conditions under which this function block can be used are as follows:

[1] CPU unit

CS/CJ Series by Omron, Version 4.0 or later

[2] Serial communication unit (SCU) CS/CJ Series by Omron

CS: CS1W-SCU**-V1 (Version 1.2 or later)

CJ: CJ1W-SCU**-V1 (Version 1.2 or later)

[3] CX Programmer

Version 7.0 or later