Part 1 Specification

Chapter 3 Gateway R unit

155

Part 1 Specification

3.9.3.5 Preset Multiple Registers (Query using FC = 10H)

Data is changed in (written to) multiple successive holding registers in the slave.

The basic query/response structures and examples of queries are shown below.

(1) Basic Query/Response Structures

[1] Query format

The query message specifies the address of the holding register (gateway register) from which to start changing

(writing) data, and the data.

Data length of 1 holding register = 1 word = 2 bytes = 16 bits

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

10 H

1

Starting address

(upper)

Arbitrary

Starting address

(lower)

Arbitrary

2

The address varies depending on the axis

arrangement.

Number of registers

(upper)

Arbitrary

Number of registers

(lower)

Arbitrary

2

Bytes

Arbitrary

1

New data 1

(upper)

Arbitrary

New data 1

(lower)

Arbitrary

1 each for upper

and lower words

2

New data 2

(upper)

Arbitrary

New data 2

(lower)

Arbitrary

1 each for upper

and lower words

2

New data 3

(upper)

Arbitrary

New data 3

(lower)

Arbitrary

1 each for upper

and lower words

2




Error check

(CRC)

16 bits

2

Based on calculation result

Trailer

None

-

Total bytes

15