Chapter 3 Gateway R unit

120

Part 1 Specification

(2) Communication Method

The Modbus protocol uses the single-master/multiple-slave communication method. Only the master can issue a query

(to start communication). The slave receives a query, performs the specified function, and returns a response message.

The master can issue a query to a specific slave or broadcast a query to all slaves.

In the case of a broadcast query, the slaves only performs the specified function and do not return a response message.

Each slave returns a response message only after receiving a query addressed specifically to the slave. The query

transmission format consists of the slave address (or broadcast specification), function code defining the request, and

data/error check fields.

The response message transmission format consists of the request check field and data/error check fields. The

transmission formats of query and response messages are shown below.

Query and response communication cycle

(3) Serial Transfer Mode

The serial transfer mode in the Modbus gateway mode is the RTU (Remote Terminal Unit) mode.

In the RTU mode, 1-byte (8-bit) data is transmitted directly, which results in greater transmission efficiency.

Query message

(from the master)

Address

Function

Data

Error check

Address

Function

Data

Error check

8 bits

8 bits

N x 8 bits

16 bits

Response message

(from the slave)

-144-