Part 1 Specification

Chapter 3 Gateway R unit

135

Part 1 Specification

[7] Read completed position number status – Axis (0)

The configuration of the completed position number register of axis (0) is shown below.

z

Query

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Starting address

(upper)

F7 H

Starting address

(lower)

0A H

2

Address of the completed position number of

axis (0)

Number of registers (upper)

00 H

Number of registers (lower)

01 H

2

Number of registers (1 register = 1 word): 1

Error check

(CRC)

Based on

calculation result

2

(92 A2)

Trailer

None

-

Total bytes

8

z

Response

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Data bytes

02 H

1

1-word register x 1 = 2 bytes

Data 1

(upper)

Arbitrary

Data 1

(lower)

Arbitrary

1 each for upper

and lower words

2

Completed position number data

Error check

(CRC)

Based on

calculation result

2

Trailer

None

-

Total bytes

7

z

Actual Example

„

Sent Query:

3F03F70A000192A2

„

Received Response: 3F03020003D180

(Explanation) The completed position number is “3.”

Address