Part 1 Specification

Chapter 3 Gateway R unit

154

Part 1 Specification

[4] Output control signals (Axis 1 = Direct numerical specification mode)

An example of control signals of axis (1) is explained.

The configuration of the control signal register of axis (1) is shown below.

The method of use is the same as in [3], except for the DIR and PUSH.

The DIR and PUSH signals are used as a set when performing push operation in the direct numerical specification

mode.

x

PUSH signal: The push mode is effective when this signal is “1.”

x

DIR signal:

This signal specifies the push direction.

“0” = Home return direction “1” = Opposite home return direction

In other conditions, the push speed corresponds to the specification of parameter No. 34, while the maximum push

amount corresponds to the specified positioning band.

A query in the push operation mode is described below.

z

Query

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

06 H

1

Starting address

(upper)

F6 H

Starting address

(lower)

13 H

2

Address of the control signal register of axis (1)

New data (data written) (upper)

30 H

New data (data written) (lower)

10 H

2

Set DIR, PUSH and SON to “1.”

Error check

(CRC)

16 bits

2

Based on calculation result (5A95)

Trailer

None

-

Total bytes

8

z

Response

If the data has been changed (written) successfully, the response is the same as the query.

z

Actual Example

„

Sent Query:

3F06F61330105A95

„

Received Response: 3F06F61330105A95

Address

-178-