Part 3 Maintenance

Chapter 1 T

roubleshooting

358

Part 3 Maintenance

Alarms are classified into two levels based on the symptoms associated.

Alarm level

ALM lamp

ALM signal logic

Condition of generation

Reset method

Operation

cancellation

Lit

“1”

After deceleration stop

Servo OFF

Input the alarm reset signal

(RES) from the PLC.

Perform a reset action from

the PC/teaching pendant.

Cold start

Lit

“1”

After deceleration stop

Servo OFF

Reconnect the power.

*

The ALM signal uses the positive logic.

After the power is turned on, this signal remains “0” while the system is normal, and turns “1” if an alarm has occurred.

(Since the signal becomes “0” when the power is cut off, it cannot be used as an interlock signal.)

„

How to reset operation-cancellation alarms

Input the alarm reset (RES) signal for 6 msec or longer.

The ALM signal will return to “0” after the above period. Confirm the “0” status and then set the RES signal to “0” (OFF).

Caution

Reset each alarm after identifying and removing its cause.

If the cause of the alarm cannot be removed, or the alarm cannot be reset even after its cause has been removed, contact

IAI.

If the same alarm generates again after a reset, the cause of the alarm has not been removed. In this case, repeating the

reset action may result in a burned motor or other undesired condition. Be sure to identify the cause and remove it before

resetting the alarm.

An alarm list for RACON and RPCON is provided on the next page.

Alarm reset (RES)

Alarm (ALM)

Alarm status

6 msec or longer

Alarm reset

-390-